Diffuser

breeze-01.jpg
BEST

Breeze Line Diffuser

Product Type Product Code
Breeze Line Diffuser(single slot)

BLDS Φd1 round/oval L(Length)
Breeze Line Diffuser(double slot)

BLDS Φd1 round/oval L(Length)

Product Overview

It is a diffuser that can control the direction of airflow with a blade. It is divided into S type and D type according to the number of slots.


Product Type & Features

Product Type S Type D Type
breeze-01
breeze-02
Number of slots 1 2
Control of Diffused Airflow Direction and Air Volume Since the direction of the airflow can be adjusted up to 45° to the left and right by using the blade,
the airflow distribution in the room can be properly maintained.
There is very little static pressure loss and air volume change due to the change in the direction of the airflow.
Structure and Appearance A blade that can control the direction of the airflow is attached. When the blade is removed, it can be used for
suction and exhaust. The diffuser is made of aluminum, which is light and sturdy, and the exterior is beautiful.
2 The diffuser and chamber (Chamber/Plenum Box) are integrated
by fixing it with screws to the mounting hooks.
Since the gasket (option) is attached to the instrument frame(option) and adheres to the ceiling surface, contamination of the ceiling surface due to suction and discharge can be prevented.
How to control airflow
breeze-04
breeze-05

Product Material & Finish

Chamber/Plenum Box Hot-dip galvanized steel sheet (GI/CGI)/Galvalume (G/L)
Diffuser Aluminum Powder coating

Product Dimension

BREEZE LINE DIFFUSER

breeze-06.jpg

* For the products other than the above specifications, please contact us.

Performance Data

Vertical Diffusion
Product Code Air volume (CMH/m) 50 60 70 80 90 100 150 200 250 300 400 500 600 700 800 900 1000 1500 2000
BLDS 1000 Static pressure loss (mmAq) 0.65 1.20 1.85 2.75 4.80 7.60 12.0
Static pressure loss (mmAq) 16 23 27 32 36 42 45
Vertical reach distance (m)*2 1.2 1.4 1.8 2.0 2.2 3.2 4.2 5.2 6.2 8.0 10.0 12.5
BLDD 1000 Static pressure loss (mmAq) 0.62 0.92 1.60 2.55 3.70 4.90 6.50 8.25
Noise level (db)*1 24 26 33 37 41 43 46 48
Vertical reach distance (m)*2 1.0 1.2 1.3 1.4 2.1 2.8 3.4 4.1 5.3 6.6 7.8 9.0 10.5 12.0


Horizontal Diffusion
Product Code Air volume (CMH/m) 50 60 70 80 90 100 150 200 250 300 400 500 600 700 800 900 1000 1500 2000
BLDS 1000 Static pressure loss (mmAq) 0.52 1.20 2.10 3.20 4.70 8.20 13.0
Static pressure loss (mmAq) 21 27 32 35 40 45
Vertical reach distance (m)*2 1.9 2.2 2.5 2.8 3.0 3.3 4.4 5.6 6.7 7.8 9.7 12.0
BLDD 1000 Static pressure loss (mmAq) 0.60 0.92 1.35 2.40 3.80 5.30 7.30 8.80
Noise level (db)*1 21 25 29 35 38 43 46 48
Vertical reach distance (m)*2 1.2 1.35 1.5 1.7 1.85 2.0 2.7 3.5 4.1 4.8 5.9 7.1 8.1 9.3 11.5


Suction
Product Code Air volume (CMH/m) 50 60 70 80 90 100 150 200 250 300 400 500 600 700 800 900 1000 1500 2000
BLDS 1000 Static pressure loss (mmAq) 0.34 0.45 0.57 0.69 1.55 2.70 4.00 5.90
Noise level (db)*1 - 15 16 17 24 32 33 40
BLDD 1000 Static pressure loss (mmAq) 0.50 0.90 1.45 2.05 3.55 5.50 7.90
Noise level (db)*1 23 26 32 35 40 45 49


Diffusion on the ceiling surface
BLDS 1000 Air volume (CMH/m) 170 195 225 250 280 305 335 360
Diffusion angle (deg) R3 9.4 9.0 8.7 8.4 8.2 8.0 7.8 7.6
Reach distance (m)*3 L3 3.9 4.5 4.5 4.8 5.1 5.1 5.4 5.7
Reach distance (m)*3 L3 35 38 41 44 46 48 50 51
Static pressure loss (mmAq) 1.78 2.54 3.56 4.57 5.59 6.68 7.87 11.9
BLDS 1000 Air volume (CMH/m) 305 360 420 475 530 585 640 700
Diffusion angle (deg) R3 9.6 9.2 9.0 8.7 8.5 8.3 8.0 7.8
Reach distance (m)*3 L3 4.8 5.1 5.4 5.7 5.7 6.0 6.0 6.3
Reach distance (m)*3 L3 36 39 43 45 48 50 52 54
Static pressure loss (mmAq) 2.29 3.30 4.32 5.59 7.37 8.59 10.4 11.9

*1 Noise level: Measured with a microphone at 45° angle from the outlet and 0.9m away (noise level reduced by 8db under indoor conditions)

*2 The vertical distance reached until the residual wind velocity of the airflow with a terminal velocity of 0.5m/s becomes 0.25m/s.

*3 The horizontal distance reached until the residual wind velocity of the airflow with a terminal velocity of 0.5m/s becomes 0.25m/s.


Vertical Rise Diffusion *
BLDS 1000 Air volume (CMH/m) 50 60 68 76 85 93 102 110
Horizontal reach distance (m)*4 2.1 2.4 2.7 2.7 3.0 3.3 3.3 3.6
BLDS 1000 Air volume (CMH/m) 93 110 128 144 161 178 195 212
Reach distance (m)*3 L3 2.7 3.0 3.3 3.6 3.6 3.9 3.9 4.2

* Data other than horizontal reach distance (TH) (=1.8m) is the same as that of vertical diffusion


Dew Point

Relationship between Air Volume and Surface Wind Velocity


Relationship between Air volume and Diffuser Length*
Length(mm) 500 1000 1500 2000 2500 3000 3500 4000
Air volume (CMH) 100 200 300 400 500 600 700 800

* Reach distance (m) and static pressure loss (mmAq) do not change depending on the length of the diffuser.

Relationship between Noise Level and Diffuser Length
Length(mm) 500 1000 1500 2000 2500 3000 3500 4000
Noise level (db) -3.0 0 +2.0 +3.0 +4.0 +5.0 +5.5 +6.0

* Reach distance (m) and static pressure loss (mmAq) do not change depending on the length of the diffuser.